BACKWARD CURVED CENTRIFUGAL FAN IN SOUNDPROOF CABINET 400ºC/2H
MANUFACTURING FEATURES
• Box manufactured in galvanised steel sheet.
• Circular inlet flange.
• Backward impeller with self-cleaning system, direct coupling motor.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation type 400ºC/2h .
• Manufactured with standard voltages: 400-460V(Y) 60Hz in three phase motors up to 3kW and 400V(D) 60Hz for higher powers and 400V for 2 speed motors.
• Exchangeable pannels
• Open drive.
APPLICATIONS
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Maximum working temperature: 60ºC.
• Removing smoke in case of fire. The motor inside the hazardous area (400 ° C / 2 h)
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0582
A | B | C | D | E | G | H | J | K | L | ØF |
---|---|---|---|---|---|---|---|---|---|---|
1000 | 1000 | 1000 | 892 | 828 | 74 | 1203 | 1153 | 828 | 758 | 628 |
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.
IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current