AXIAL JET FAN 400ºC/2h
MANUFACTURING FEATURES:
The JF models are composed of an axial fan and two silencers.
FAN:
• Axial fan with galvanized steel casing. The connection box is accessible by the side from a removable door.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation, CERTIFIED 400ºc/2h. Standard voltages 400V(Y) 50Hz for 1 speed motors and 400V 50Hz for 2 speed motors.
SILENCERS:
• Casing in galvanized steel. Inner duct made of perforated galvanized steel sheet. The silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.
• Unidirectional VORT JET-A LP F400 UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.
• Reversible VORT JET-A LP F400 RE is equipped with protection guards on both sides.
APPLICATIONS:
• Conceived for car parkings and large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively. An optimized design minimizes the height needed for their installation and assures a silent operation.
• Maximum working temperature: 60ºC.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPD-1325
A | B | C | D | E | F | G | H | I | J | L | M | ØK | Thrust (N) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
2415 | 758 | 440,5 | 1025 | 720 | 664 | 434 | 506 | 233 | 20 | 122 | 365 | 15 | 48/12 |
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.