fan image
Model
CRC-A 40/6 T
Code
30112

CRC-A 40/6 T

MEDIUM PRESSURE FAN WITH FORWARD IMPELLER AND IN PLASTIC CONSTRUCTION

MANUFACTURING FEATURES:

•Housing made of PP plastic (for models size 35 and equal to or greater than size 45) other models PE casing
• Forward curved impeller in PP plastic.
• Motor support made of rolled steel sheet with polyester powder finishing coat.
• Stainless steel nuts and bolts.
• Standard asynchronous squirrel-cage motor, IP-55, class F insulation. Standard voltages 230/400V 50Hz.

• Available positions (to be indicated in case of order): LG270, LG0, LG45, LG90, LG135, LG180, LG225, LG315, RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315.
• The indicated codes correspond to the model in position LG270

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Corrosive air transport.
• Chemical and petrochemical industry.
• Laboratories and gas cabinets.
• Maximum temperature of transported air: If it is clean air 70ºC, other depends on the gas (see table in documentation)

UNDER REQUEST:

• Single phase motors (up to 1,1kW).
• 60Hz  fans and special voltages fans.
• 2 speed motors.
• Stainless steel motor support.
• Casing made of PP (for models taht is not a standard material).

Fan

Max flow
1670 m³/h
Weight
28 Kg

Motor

Power
0.25 kW
RPM Motor
900
I max. 230 V
1,5
I max. 400 V
0,87
Size
71
Efficiency
59 %
FP
0.7
CRC-A 40/6 T
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

CRC-A 40/6 T

Dimensions scheme
A B C E F G H I L N ØS P Q R
290 380 40 250 194 265 80 495 330 220 330 11 170 250 365

CRC-A 40/6 T

Electrical scheme

CRC-A 40/6 T

Model
SWT 25 3P
Code
21673
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
FLC1-F400 25
Code
21987
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
FJ-F400
Code
21669
Information
ANTI-VIBRATION JOINT

MANUFACTURING FEATURES

• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.

Model
IREM INVERTER 230 2.5A
Code
12872
Information
FREQUENCY SPEED CONTROLLER

Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.

IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
IRET INVERTER 400 1.2A
Code
12876
Information
FREQUENCY SPEED CONTROLLER

Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.

IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
NRD-F400 (GENERIC)
Code
Information
ANTI-VIBRATION RUBBER BLOCK

MANUFACTURING FEATURES

• Support of great radial and axial elasticity.
• These low-profile, compact and elastic supports control the three directions of movement with large deformations in the rubber.
• It consists of two parallel armour adhered to the bell-shaped rubber and by a base with handles.
• These supports with handles have a threaded hole in their upper frame and are easy to install and fix.
• The steel protection washer allows it to withstand overloads by increasing its rigidity and protects the rubber from dripping hydrocarbons.
• Elastomer type NR or high quality elastomer. Working temperatures between -40ºC and + 70º C.
• Taking into account the tolerances of hardness in the elastomers, the mechanical characteristics of these series may differ.
• Range of 6 sizes and 3 different hardnesses (45-60-75) to fit a load range between 2 Kg and 1300 Kg.
      1. Soft: hardness A 45
      2. Average: hardness B 60
      3. Hard: hardness C 75

APPLICATIONS

• Very appropriate in the elastic suspensions of machines that present vibrations of horizontal components.

Model
XS-F400 (GENERIC)
Code
Information
ANTI-VIBRATION SPRING BLOCK

MANUFACTURING FEATURES

• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:

Arrow (mm.)          r.p.m.
    20 mm          >600 r.p.m.
    30 mm          >500 r.p.m.

• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.

APPLICATION

• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.