CENTRIFUGAL JET FAN 300ºC/2h
MANUFACTURING FEATURES
Centrifugal powerful jet fan with low profile conceived for car parkings, working inside
the hazardous area and remove wide air volume in car parks 300ºC/2h.
FAN
• Galvanized steel sheet casing.
• Strong backward impeller with self-cleaning system made of strong galvanized steel sheet.
• External wiring box.
• Inlet protection.
• Feet included.
MOTOR
• Class H insulation, S1 continuous use and S2 emergency use, with bearing balls,
IP-55 protection, 2 speeds.
• 400V 4/8 poles Dalhander three phase motor.
• Maximum working temperature:
• S1 -> -20ºC +60ºC.
• S2 -> 300ºC / 2h.
A | B | C | D | E | F | H | I | K | L | Thrust (N) |
---|---|---|---|---|---|---|---|---|---|---|
1230 | 250 | 870 | 281 | 963 | 922 | 600 | 275 | 13 | 3 | 50/13 |
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.