AXIAL FAN 400ºC/2h
MANUFACTURING FEATURES
• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 400ºC/2h. Standard voltages 400V(Y) 50Hz in three phase motors up to 3kW and 400V(D) 50Hz for higher powers and 2 speed motors. IE3 efficiency motor from 0,75kW up to 45kW in single speed
APPLICATIONS
Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Maximum working temperature: 60ºC.
UNDER REQUEST
• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0914
C (Mot.T.100L) | C (Mot.T.100L) | C (Mot.T.63) | C (Mot.T.71) | C (Mot.T.80) | C (Mot.T.90L) | C (Mot.T.90L) | C (Mot.T.90S) | E | O | ØA | ØB | ØD | ØJ |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
418 | 418 | 328 | 328 | 347 | 387 | 387 | 362 | 165 | 8X45º | 525 | 500 | 452 | 12 |
MANUFACTURING FRATURES
• Protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.
MANUFACTURING FEATURES
• For axial (inlet and outlet) and centrifugal (inlet) fans.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.
MANUFACTURING FEATURES
• Square support frame for MHP fans.
• Made of steel and protected against corrosion with polyester resin powder.
MANUFACTURING FEATURES
• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.
• Overpressure backward damper for facade made of extruded aluminum and standard natural aluminum finishing.
• It incorporates weatherstrip in the fins to achieve greater efficiency in the closure and noise damping.
• Maintains overpressure or depression inside a room with respect to the outside or other adjacent rooms.
• Drills incorporated in frame for wall or duct fixing with screws or rivets.
• Recommended maximum air passage speed 6m/s. maximum temperature of 80ºC.
MANUFACTURING FEATURES
• Circular-circular coupling flange through anti-vibration canvas.
• Fire resistance M0: from -50ºC to +200ºC in continuous and 400ºC/2h
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.