BACKWARD CENTRIFUGAL PLUG FAN TYPE, DIRECT DRIVEN, FOR RECIRCULATION OF HOT GASES
MANUFACTURING FEATURES:
• Direct driven centrifugal medium pressure fan, type plug fan.
• Insulated casing made of carbon laminated steel, protected against corrosion by powder polyester coat. Finish C3.
• Thermal insulation with high density rock wool, 145Kg/m3, thickness 50mm
• Self-cleaning and reinforced impeller with high performance backward (reaction) blades made of carbon laminated steel dynamically balanced to minimize noise and vibrations painted In black heat-resistant paint coating.
• IE3 Motor for continuous operation (S1) Squirrel cage standardized asynchronous IEC motor with IP-55 protection and Class F electrical insulation. Standard voltages 230/400V 50Hz for three phase motors Up to 4kW and 400/690V 50Hz for higher powers.
• Motor with flange (B5).
• Maximum continuous working temperature ambient (motor): 60ºC.
• Suitable for transferring gases from -40ºC to 250ºC in continuous.
• Integrated cooling impeller
APPLICATIONS:
Plug-type installation made for the recirculation of gases in:
⦁ Ovens
⦁ Boilers
⦁ Paint booths
⦁ Drying of tobacco, barley, ceramic, glass and wood leaves
⦁ Insulated thermal cameras subjected to temperature control
⦁ Burners and incinerators
⦁ Melting furnaces
ON DEMAND:
⦁ Fans for special voltages
⦁ 2 Speed motor, Inox 304 or Inox 316
⦁ Sparking proof construction
⦁ Other sizes
⦁ Other motors according to customer requeriment
±B | A | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|
580 | 970 | 873 | 570.5 | 150 | 314 | 233 | 380 |
Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.
IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current