BACKWARD CENTRIFUGAL PLUG FAN TYPE, DIRECT DRIVEN, FOR RECIRCULATION OF HOT GASES
MANUFACTURING FEATURES:
• Direct driven centrifugal medium pressure fan, type plug fan.
• Insulated casing made of carbon laminated steel, protected against corrosion by powder polyester coat. Finish C3.
• Thermal insulation with high density rock wool, 145Kg/m3, thickness 50mm
• Self-cleaning and reinforced impeller with high performance backward (reaction) blades made of carbon laminated steel dynamically balanced to minimize noise and vibrations painted In black heat-resistant paint coating.
• IE3 Motor for continuous operation (S1) Squirrel cage standardized asynchronous IEC motor with IP-55 protection and Class F electrical insulation. Standard voltages 230/400V 50Hz for three phase motors Up to 4kW and 400/690V 50Hz for higher powers.
• Motor with flange (B5).
• Maximum continuous working temperature ambient (motor): 60ºC.
• Suitable for transferring gases from -40ºC to 250ºC in continuous.
• Integrated cooling impeller
APPLICATIONS:
Plug-type installation made for the recirculation of gases in:
⦁ Ovens
⦁ Boilers
⦁ Paint booths
⦁ Drying of tobacco, barley, ceramic, glass and wood leaves
⦁ Insulated thermal cameras subjected to temperature control
⦁ Burners and incinerators
⦁ Melting furnaces
ON DEMAND:
⦁ Fans for special voltages
⦁ 2 Speed motor, Inox 304 or Inox 316
⦁ Sparking proof construction
⦁ Other sizes
⦁ Other motors according to customer requeriment
±B | A | C | D | E | F | G | H |
---|---|---|---|---|---|---|---|
580 | 801 | 723 | 399 | 150 | 220 | 192 | 311.5 |
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.
IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III
EMC filter incorporated for models from 47A (included)
*Lineal load rated current
**Quadratic load rated current