BELT DRIVEN BACKWARD CENTRIFUGAL IN SOUNDPROOF CABINET 400ºC/2H
MANUFACTURING FEATURES:
• VORTICENT CMS STB range fans assembled in soundproof cabinets with insulated panels.
• Fan assembled on antivibration mountings.
• Simple inlet, backward impeller with self-cleaning system.
• Supplied with motor, pulleys and belts.
• Gland connection included.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
APPLICATIONS:
Designed for inline installation, indoor or outdoor assembly, they are suitable for:
• Air renewal in buildings and industries.
• Smoke emergency exhaust with motor outside the hazardous area (400ºC/2h certified).
• Industrial and professional kitchen hoods.
• Maximum working temperature: carried air 130ºC; environment 60ºC.
UNDER REQUEST:
• Special voltages.
• 2 speed motors.
• Orentation:
- LG90 (horizontal).
- LG0 (vertical outlet).
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-1371
A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | ØR | P | Q | S | T | U | V | W |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1323 | 1003 | 692 | 1215,7 | 900 | 587 | 1149,5 | 831,5 | 521 | 1159,5 | 841 | 1219,5 | 890 | 100 | 328 | 448 | 40,5 | 60 | 375 | 587,7 | 60 | 573 | 310 |
MANUFACTURING FEATURES
• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.
MANUFACTURING FEATURES
• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.
MANUFACTURING FEATURES
• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.
*Máx. thermal current air (A)
Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.
MANUFACTURING FEATURES
• Support of great radial and axial elasticity.
• These low-profile, compact and elastic supports control the three directions of movement with large deformations in the rubber.
• It consists of two parallel armour adhered to the bell-shaped rubber and by a base with handles.
• These supports with handles have a threaded hole in their upper frame and are easy to install and fix.
• The steel protection washer allows it to withstand overloads by increasing its rigidity and protects the rubber from dripping hydrocarbons.
• Elastomer type NR or high quality elastomer. Working temperatures between -40ºC and + 70º C.
• Taking into account the tolerances of hardness in the elastomers, the mechanical characteristics of these series may differ.
• Range of 6 sizes and 3 different hardnesses (45-60-75) to fit a load range between 2 Kg and 1300 Kg.
1. Soft: hardness A 45
2. Average: hardness B 60
3. Hard: hardness C 75
APPLICATIONS
• Very appropriate in the elastic suspensions of machines that present vibrations of horizontal components.
MANUFACTURING FEATURES
• Metal insulators designed to work with compression with 85% insulation according to the following arrows (travel in mm) and rpm:
Arrow (mm.) r.p.m.
20 mm >600 r.p.m.
30 mm >500 r.p.m.
• Made of high quality elastic steel, with rectangular base and rubber mat to improve the grip. It treats of a resistant product and easy assembly, that avoids all type of vibrations of the fans to the structure of the premises.
• Operating temperature from -45 ° C to + 120 ° C.
APPLICATION
• To install under machines with rotating components, ventilation groups, fans, ventilation boxes, etc.