VORTICEL MHP F400
Model
VORTICEL MHP 1124 T (A:4) F400
Code

VORTICEL MHP 1124 T (A:4) F400

AXIAL FAN 400ºC/2h

MANUFACTURING FEATURES

• Axial fan with circular reinforced frame.
• Modular motor-impeller assembly.
• Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Standard asynchronous squirrel cage motor with IP-55 protection and Class H insulation certified 400ºC/2h. Standard voltages 400V(Y) 50Hz in three phase motors up to 3kW and 400V(D) 50Hz for higher powers and 2 speed motors. IE3 efficiency motor from 0,75kW up to 45kW in single speed

APPLICATIONS

Designed for wall or duct installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Maximum working temperature: 60ºC.

UNDER REQUEST

• B Form impeller (air flow from impeller to motor).
• 100% reversible impeller.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0914

Fan

Max flow
92110 m³/h
VORTICEL MHP 1124 T (A:4) F400
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

VORTICEL MHP 1124 T (A:4) F400

Dimensions scheme
C (Mot.T.132) C (Mot.T.160L) C (Mot.T.160M) C (Mot.T.180L) C (Mot.T.180L) C (Mot.T.180M) C (Mot.T.200) C (Mot.T.200) C (Mot.T.225) C (Mot.T.225) E O ØA ØB ØD ØJ
760 760 760 780 780 761 864 864 949 949 340 16x22,5º 1234 1190 1132 12

VORTICEL MHP 1124 T (A:4) F400

Electrical scheme

VORTICEL MHP 1124 T (A:4) F400

Model
BA-400 112
Code
Information
ANTI-VIBRATING FLANGE 400º/2H

MANUFACTURING FEATURES

• Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations to the installation.
• 160 mm width and supplied with 2 fixing clamps.
• Certified according to the European standard EN 12101-3 400ºC/2h. Fire classification: M0.

Model
FJ-F450
Code
21669
Information
ANTI-VIBRATION JOINT

MANUFACTURING FEATURES

• Flexible joint to clinch the fan to the duct.
• Avoids transmission of vibrations for circular and rectangular connection.
• Dimensions: two metallic flanges of 45mm each one and a flexible flange of 60mm.
• The reel is 30,5m lenght.
• Maximum pressure: 20 mmca.
• Fire resistance M0 from -50ºC to +200ºC in continuous and 400ºC/2h.

Model
FLCC-F400 112
Code
Information
CIRCULAR-CIRCULAR ANTI-VIBRATION FLANGE

MANUFACTURING FEATURES

• Circular-circular coupling flange through anti-vibration canvas.
• Fire resistance M0: from -50ºC to +200ºC in continuous and 400ºC/2h

Model
MFL-F400 1120
Code
21705
Information
CONECTION FLANGE

MANUFACTURING FEATURES

• For axial (inlet and outlet) and centrifugal (inlet) fans.

UNDER REQUEST

• Versions in stainless 304 and stainless 316.

Model
IREM/IRET INVERTER (GENERIC)
Code
Information
FREQUENCY SPEED CONTROLLER

Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.

IREM/IRET INVERTER 230: Entrance 230V I, exit 230V III
IREM/IRET INVERTER 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
SWT (GENERIC)
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

Model
SWT F400 (GENERIC)
Code
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category
Equips two auxiliary contact.

Model
MSC3-F400 (generic)
Code
Information
INLET PROTECTION GUARD FOR AXIAL FANS

MANUFACTURING FRATURES

• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.

UNDER REQUEST

• Stainless guard 304 or 316 with electro-polished finishing coat.