BACKWARD CURVED CENTRIFUGAL FAN IN SOUNDPROOF CABINET 400ºC/2H
MANUFACTURING FEATURES
• Box manufactured in galvanised steel sheet.
• Circular inlet flange.
• Backward impeller with self-cleaning system, direct coupling motor.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation type 400ºC/2h .
• Manufactured with standard voltages: 400V(Y) 50Hz in three phase motors up to 3kW and 400V(D) 50Hz for higher powers and 400V for 2 speed motors.
• Exchangeable pannels
• Open drive.
APPLICATIONS
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Maximum working temperature: 60ºC.
• Removing smoke in case of fire. The motor inside the hazardous area (400 ° C / 2 h)
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0582
Fan sheet |
|||
---|---|---|---|
Fan type |
Unit for non-residential ventilation (LOT 6) |
||
Tipology |
Unidirectional | ||
Other |
None |
||
Type of driver | None | ||
Values | Requirements 2018 | ||
Max. efficiency (%) |
49.09 | 37.44 | |
Eff. heat recovery (%) |
- | ||
Absorbed power (kW) | 0.479 | ||
Flow (m³/h) |
3823.35 | ||
Static pressure (Pa) |
208.9 | ||
Speed (m/s) |
5.45 | ||
SFP |
451.38 |